Copper XLPE Cable

XLPE Cables - Single Core, Aluminum Conductor

Application:

For mains, sub mains and sub circuits unenclosed, enclosed in conduit, buried direct or in underground ducts for buildings and industrial plants where not subject to mechanical stress. Suitable where space is at a premium and/or where conditions of overload may occur.

Conductor: Plain Aluminium
Insulation: XLPE X-90
Sheath: PVC 5V-90
Voltage: 0.6/1KV
Standards: AS/NZS3808 and AS/NZS 5000.1
Normal Operating Temperature: 90°C

Typical Features

Code

Conductor

Insulation
Thick
mm

Sheath
Thickness
mm

OD±
10%

Min
Bending
Radius mm

Standard Packing

Order
Now

mm2

No./mm

100m

500m

ALX1160

16

7/1.70

0.7

1.4

9.4

118

 

ALX1250

25

7/2.14

0.9

1.4

11.1

138

 

ALX1350

35

7/2.52

0.9

1.4

12.2

150

 

ALX1500

50

19/1.78

1

1.4

13.8

170

 

ALX1700

70

19/2.14

1.1

1.4

15.8

192

 

ALX1950

95

19/2.52

1.1

1.5

17.9

216

 

ALX11200

120

37/2.03

1.2

1.5

19.7

240

 

 

ALX11500

150

37/2.25

1.4

1.6

21.8

264

 

 

ALX11850

185

37/2.52

1.6

1.6

24.1

288

 

 

ALX12400

240

61/2.25

1.7

1.7

27.1

324

 

 

 

ALX13000

300

61/2.52

1.8

1.8

30

360

 

 

 

ALX14000

400

61/2.85

2

1.9

33.6

410

 

 

 

ALX15000

500

61/3.20

2.2

2

37.3

450

 

 

 

ALX16300

630

91/2.93

2.4

2.2

41.6

540

 

 

 
*Some items are subject to minimum order Quantity. Please contact our sales team for details
* Conductors are circular compacted

Current Rating and Electrical Characteristics

Conductor Nom. Area   mm2Single Phase
Current Rating (a)
Single Phase
Voltage drop
mV/A.m
Max.Cond. DC.
Resistance
@ 20 ©/km
Insulation
Resistance
¥M ©.km
In conduit
in air
Buried in
ducts
16 53 72 4.91 1.91 0.431
25 67 91 3.08 1.2 0.444
35 89 105 2.24 0.868 0.379
50 117 135 1.65 0.641 0.354
70 149 160 1.15 0.443 0.323
95 178 195 0.84 0.32 0.29
120 225 240 0.672 0.253 0.283
150 267 290 0.557 0.206 0.294
185 315 335 0.455 0.164 0.303
240 355 375 0.363 0.125 0.283
300 405 435 0.307 0.1 0.262
400 478 510 0.261 0.0778 0.243
500 535 580 0.228 0.0605 0.223
630 639 670 0.204 0.0469 0.187

 

(a)

Based on 40°C ambient air temperature and where applicable, burial depth of 0.5m, soil temperature of 25°C and soil resistivity of 1.2°C m/W.

(b)

For single phase voltage drop, multiply by 1.155

 

The above information is from the following sources:

 

AS/NZ 3008.1.1
AS/NZS 1125

 

For current rating using other installation conditions refer to AS/NZS3008.1.1
Do not install in direct contact with polystyrene or polyurethane insulation materials